Designing ventilation systems for different spaces

According to the Ashare standard, for the ventilation of different spaces with different applications, a certain number of air changes per hour is recommended so that the air quality inside the building is acceptable for the occupants. This standard is based on the reduction of pollution in the ambient air. The amount of air required for different spaces is calculated from the relationship Q=V x n, where Q is the air volume (…, cfm, m3/h), V is the volume of the desired space (ft3, m3) and n is the number of times Air exchange in hours for different spaces.

target environmentAir exchange times n-1/h
All spaces in generalAt least 4
conference hall6-4
Halls8-15
Bakery20-30
Bank4-10
bar20-30
Barber Shop6-10
Hair Salons6-10
Steam boiler room15-20
Cafeteria12-15
Churches8-15
classrooms6-20
GYM20-30
computer room15-20
Court4-10
dance hall6-9
Dental centers8-12
Shopping Center6-10
dinning salon12-15
Reception rooms12
clothing shop6-10
Pharmacy6-10
engine room (electrical room)4-6
Factories with non-polluting machines2-4
Factories with machines that produce steam and moisture10-15
fire station4-10
Casting15-20
Repair garage20-30
Warehouse garage4-6
Houses – ventilation at night10-18
Hospital rooms4-6
Jewelry6-10
kitchen15-60
laundry10-15
public Library4
Night clubs20-30
Car stores6-12
Markets6-10
Medical centers8-12
Medical clinics8-12
Medical offices8-12
Paper factory15-20
Textile factories4
Textile dyeing factories15-20
City Hall4-10
museums12-15
Public offices3
Private offices4
Paint shop10-15
Dark room photography10-15
Police stations4-10
Post offices4-10
Aviculture6-10
Power house (swimming pool and sauna)5
Railway shops4
Restaurant8-12
retail6-10
School classes4-12
Shoes stores6-10
shopping center6-10
woodcraft5
Substation5-10
Super Market4-10
Swimming pool20-30
Textile factories4
theaters8-15
Transformer room10-30
Room of electric turbines5-10
storeroom2